EasyManua.ls Logo

AUMA ACV 01.2 - Signal Range of Analogue Output 1

AUMA ACV 01.2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The zero point is in the centre of the selected output range (10 mA or 12 mA). The
torque in direction CLOSE is indicated with 0 10 mA or 4 12 mA, the torque in
direction OPEN with 10 20 mA or 12 20 mA. For 127 % of the maximum nominal
output torque, 0 or 4 mA are indicated in direction CLOSE, and 20 mA are indicated
in direction OPEN.
Figure 33: Actual torque value
127 %= maximum nominal torque in end position CLOSED reached
+127 %= maximum nominal torque in end position OPEN reached
Input AIN 1
Analogue value transmitted via AIN1 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0 20 mA) is connected to the analogue input
AIN 1.
Input AIN 2
Analogue value transmitted via AIN 2 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0 20 mA) is connected to the analogue input
AIN 2.
Speed target value
Speed setpoint.
Temp. ctrls norm.
Actuator controls temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Temp. ctrl unit norm
Control unit temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Total accel. in %
Total acceleration in percent of oscillation/vibration measurement 0 % = 0.000 g =
0/4 mA; 100 % = 4.000 g = 20 mA
Condition: MWG position transmitter in actuator.
5.3.2. Signal range of analogue output 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal range AOUT1 M0129
Default value: 0 - 20 mA
Setting values:
0 - 20 mA
Analogue output 1 generates a 0 20 mA signal.
4 - 20 mA
Analogue output 1 generates a 4 20 mA signal.
20 - 0 mA
Analogue output 1 generates a 20 0 mA signal.
20 - 4 mA
Analogue output 1 generates a 20 4 mA signal.
X to Y mA
The signal range (X-Y) of the analogue output can be freely configured using two
parameters.
5.3.3. Adjustment of analogue output 1
Initial values and end values of the signal range can be corrected by ± 10 % of the
maximum value range (20 mA)
Example: Parameter Signal range AOUT1 = 4 - 20 mA
The initial value (4 mA) can be adapted within a range of 2 mA to 6 mA.
29
Actuator controls
ACV 01.2/ACVExC 01.2 Signals (output signals)

Table of Contents

Other manuals for AUMA ACV 01.2

Related product manuals