Not ready REMOTE / NAMUR function check
RemedyDescription/causeDisplay (App or CDT)
Use AUMA Assistant App or AUMA CDT to visualise
the individual signals by means of the Diagnostics
menu.
●
Check operation commands (reset/clear all op-
eration commands and send one operation
command only).
●
Activate parameter PRM_1169 Positioner.
●
Check setpoint.
Collective signal 13:
Possible causes:
●
Several operation commands (e.g. OPEN and
CLOSE simultaneously, or OPEN and SET-
POINT operation simultaneously)
●
A setpoint is present and the positioner is not
active
Wrong operation cmd
Correct operation command, i.e. delete and set
anew.
Incorrect operation command REMOTE1I
Correct operation command.
Wrong operation command fieldbus
Check availability of the function (menu Activation)Setpoint position disabled
46
PF-Q80 – PF-Q600
Corrective actions