Control
Parallel
Profibus DP
Profinet
Modbus RTU
Modbus TCP/IP
EtherNet/IP
Foundation Fieldbus
HART
DeviceNet
Multi-turn actuators
SA 07.2 SA 16.2
SAR 07.2 SAR 16.2
Control unit: electronic (MWG)
with actuator controls
AC 01.2 Non-Intrusive
Assembly and commissioningOperation instructions

Table of Contents

Other manuals for AUMA SAR 16.2

Questions and Answers

  • B
    benjamin93Aug 7, 2025
    Why does my AUMA SAR 16.2 Controller display 'Phase fault'?
    • L
      Lori PhillipsAug 7, 2025
      The 'Phase fault' error on your AUMA Controller indicates that one phase of the power supply is missing, meaning the controls are not receiving mains voltage. To resolve this, test and connect all phases of the power supply.
  • M
    Mr. Joseph Hart MDAug 11, 2025
    What to do if AUMA Controller shows 'Incorrect phase seq'?
    • D
      Darren BrownAug 12, 2025
      If your AUMA Controller displays 'Incorrect phase seq', it means the phase conductors L1, L2, and L3 are connected in the wrong sequence. To fix this, correct the sequence by exchanging two of the phases.
  • J
    Jacob SanchezAug 16, 2025
    What to do if AUMA SAR 16.2 displays 'Torque fault CLOSE Torque fault OPEN'?
    • A
      Andrea PatelAug 16, 2025
      The 'Torque fault CLOSE Torque fault OPEN' error on your AUMA controller indicates a torque fault in the CLOSE or OPEN directions, or simultaneously in both. Try executing an operation command in the opposite direction. Also, verify the torque switching setting and check for any foreign objects preventing the valve from closing. There may also be problems with the valve itself.
  • J
    Jennifer McdanielAug 20, 2025
    What does 'Wrn controls temp' mean on my AUMA SAR 16.2 and how to fix it?
    • C
      Christopher HuffmanAug 20, 2025
      The 'Wrn controls temp' warning on your AUMA Controller indicates that the temperature inside the controls housing is too high, exceeding the specified temperature range. Allow the controls to cool down. Check the service conditions. You can view the current temperature display under Diagnostic M0022>Device temperatures M0524>Temp. controls.
  • M
    Michael SullivanAug 25, 2025
    How to resolve 'Thermal fault' on AUMA SAR 16.2 Controller?
    • D
      Darrell JohnsonAug 25, 2025
      The 'Thermal fault' on your AUMA Controller is caused by the motor protection tripping. To resolve this, allow the system to cool down and wait.
  • A
    alexandersantiagoAug 29, 2025
    What does 'IE 24 V AC' mean on my AUMA SAR 16.2 and how to fix it?
    • A
      Amy ReedAug 29, 2025
      The 'IE 24 V AC' error on your AUMA Controller indicates a fault in the internal 24 V DC power supply, meaning the safety-relevant part of the controls is without power. Check the power supply to resolve this issue.
  • M
    Michelle ClarkeSep 2, 2025
    What does 'Wrn range act.pos.' mean on AUMA SAR 16.2?
    • I
      Ivan WashingtonSep 2, 2025
      The 'Wrn range act.pos.' warning on your AUMA Controller means the current position feedback signal range is outside the permissible range, or both limit switches (OPEN and CLOSED) are operated simultaneously. This can also indicate a defect in the actuator mechanics. Verify the reduction gearing settings within the actuator.

AUMA SAR 16.2 Specifications

General IconGeneral
TypeSAR 16.2
Housing materialAluminium
Output speed4 to 180 rpm
Protection classIP68
ControlModulating
Ambient temperature-25 °C to +70 °C