Questions and Answers

  • M
    matthewsnyderAug 7, 2025
    Why does my AUMA SAR 07.2 display 'Phase fault'?
    • K
      Kristina ThompsonAug 7, 2025
      The 'Phase fault' error on your AUMA Controller indicates that one phase of the power supply is missing, meaning the controls are not receiving mains voltage. To resolve this, test and connect all phases of the power supply.
  • R
    Richard BarreraAug 11, 2025
    What to do if AUMA Controller shows 'Incorrect phase seq'?
    • B
      Brianna MarksAug 11, 2025
      If your AUMA Controller displays 'Incorrect phase seq', it means the phase conductors L1, L2, and L3 are connected in the wrong sequence. To fix this, correct the sequence by exchanging two of the phases.
  • L
    Lisa McintyreAug 16, 2025
    What to do if AUMA SAR 07.2 displays 'Torque fault CLOSE Torque fault OPEN'?
    • M
      Melissa BellAug 16, 2025
      The 'Torque fault CLOSE Torque fault OPEN' error on your AUMA controller indicates a torque fault in the CLOSE or OPEN directions, or simultaneously in both. Try executing an operation command in the opposite direction. Also, verify the torque switching setting and check for any foreign objects preventing the valve from closing. There may also be problems with the valve itself.
  • H
    hernandezivanAug 20, 2025
    What does 'Wrn controls temp' mean on my AUMA SAR 07.2 and how to fix it?
    • J
      Jonathan DavisAug 20, 2025
      The 'Wrn controls temp' warning on your AUMA Controller indicates that the temperature inside the controls housing is too high, exceeding the specified temperature range. Allow the controls to cool down. Check the service conditions. You can view the current temperature display under Diagnostic M0022>Device temperatures M0524>Temp. controls.
  • P
    Phyllis LawrenceAug 25, 2025
    How to resolve 'Thermal fault' on AUMA Controller?
    • M
      Michael HunterAug 25, 2025
      The 'Thermal fault' on your AUMA Controller is caused by the motor protection tripping. To resolve this, allow the system to cool down and wait.
  • M
    Michael WalshAug 28, 2025
    What does 'IE 24 V AC' mean on my AUMA SAR 07.2 Controller and how to fix it?
    • C
      Christopher TaylorAug 29, 2025
      The 'IE 24 V AC' error on your AUMA Controller indicates a fault in the internal 24 V DC power supply, meaning the safety-relevant part of the controls is without power. Check the power supply to resolve this issue.
  • J
    Joseph ColemanSep 2, 2025
    What does 'Wrn range act.pos.' mean on AUMA SAR 07.2 Controller?
    • J
      John BarrSep 2, 2025
      The 'Wrn range act.pos.' warning on your AUMA Controller means the current position feedback signal range is outside the permissible range, or both limit switches (OPEN and CLOSED) are operated simultaneously. This can also indicate a defect in the actuator mechanics. Verify the reduction gearing settings within the actuator.

AUMA SAR 07.2 Specifications

General IconGeneral
Type of actuatorMulti-turn actuator
Protection classIP68
Output speed4 to 180 rpm
Ambient temperature-25°C to +70°C
Housing materialAluminum