5.4.2. Cable connection
Table 16:
Terminal cross sections and tightening torques
Connection typeTerminal cross sectionsDesignation
Screw-type terminals
Tightening torque =
1.2 1.5 Nm
Flexible or solid:
0.25 10.0 mm
2
(for one wire per terminal)
Flexible:
2 x 0.25 4 mm
2
(for two wires per terminal)
Power contacts
(U1, V1, W1, U2, V2, W2)
PE connection
Spring clamp terminalsFlexible or solid:
0.25 2.5 mm
2
(for one wire per terminal)
2 x 0.25 0.75 mm
2
(for two wires per termin-
al)
Control contacts
(1 to 36, 37 to 50)
Ring lug/U-bracket
Tightening torque = 3 4
Nm
2 x M6 for cables with M6 ring lug or with U-
bracket for up to two wires with
1.5 mm
2
10 mm
2
Protective earth connection
within frame (customer connec-
tion)
1. Remove cable sheathing in a length of 250 300 mm.
2. Insert the wires into the cable glands.
3. Fasten cable glands with the specified torque to ensure required enclosure
protection.
Information: For shielded cables: Link the cable shield end via the cable gland
to the housing (earthing).
4. Strip wires:
4.1 Remove wire sheathing of control cables (1...50) in a length of approx. 10
mm
4.2 Remove wire sheathing of motor cables (U, V, W) in a length of approx.
12 mm
5. For flexible cables: Use wire end sleeves according to DIN 46228. For spring
clamp terminals, connection is also possible without wire end sleeves.
Information: For two flexible wires per terminal, a joint wire end sleeve must
be used.
6. Connect cables according to order-related wiring diagram.
Figure 29: Connect cables to terminal carrier
[1] Fitting control cables into spring clamp terminals
[2] Tightening power terminals
Information
For service purposes, each spring clamp terminal for control cables is equipped with
a test contact located above the numbering.
34
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Control unit - electromechanical
Electrical connection ACExC 01.2 Intrusive

Table of Contents

Other manuals for AUMA SQEx 05.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SQEx 05.2 and is the answer not in the manual?

AUMA SQEx 05.2 Specifications

General IconGeneral
BrandAUMA
ModelSQEx 05.2
CategoryController
LanguageEnglish

Related product manuals