ZN551 Control Module • Rev. 3/17/2005 18 © 2005 Automated Logic Corporation
If Run LED shows... And Error LED shows... Status is..
14 flashes per second
14 flashes per second,
alternating with Run LED
Brownout
Manufacture date
When troubleshooting, you may need to know a control module's
manufacture date.
Obtain the manufacture
date from a...
Notes
Module status report (modstat) To obtain a modstat in WebCTRL:
1. Select the control module in the NET tree.
2. Press Ctrl+M.
3. Type modstat.
4. Click OK.
The report shows the date under Main board
hardware.
Sticker on the back of the
main control module board
The first three characters on the sticker show the
control module type. The next three characters
show the year, month, and day of manufacture.
(The month digit is in hexadecimal format.)