EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - F2-02 DAS-2 2-Channel 0-5 V, 0-10 V Isolated Analog Output Module

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–68
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-02DAS-2 2-Channel 0-5V, 0-10V Isolated Analog Output Module
Number of Channels
2, isolated
Output Ranges
0-5V, 0-10V
Resolution
16 bit (1 in 65536)
Output Type
Sourced through external loop supply
Digital Output Points
Required
32 (Y) output points
(16 binary data bits, 2 channel ID bits)
Isolation Voltage
±750 V continuous, channel to channel,
channel to logic
Base Power Required 5VDC
60 mA
External Power Supply
21.6-26.4 VDC @ 60 mA per channel
Load Impedance
2 k min
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240, D2-
250(-1) and D2-260 CPUs)
Conversion Settling Time
3ms to 0.1% of full scale
Linearity Error (end to end)
±10 count (±0.015% of full scale) maximum
Gain Calibration Error
±32 counts (±0.05%)
Offset Calibration Error
±13 counts (±0.02%)
Output Drift
50 ppm/ºC
Maximum Inaccuracy
0.07% @ 25ºC (77ºF)
0.18% 0 to 60ºC (32º to 140ºF)
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON

Table of Contents