EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - F2-02 DA-2 2-Channel Voltage Analog Output Module

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–64
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
This module requires a 24 VDC user power supply for operation. See the F2-02DA-2L on
the next page if you want to use a 12 VDC supply. All other specifications are the same.
Number of Channels
2
Output Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
Output Type
Single ended, 1 common
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 2 channel ID bits)
Peak Output Voltage
15 VDC (clamped by transient voltage
suppressor)
Load Impedance
2000 minimum
Load Capacitance
.01 µF maximum
PLC Update Rate
1 channel per scan maximum D2-230 CPU
2 channels per scan maximum (D2-240, D2-
250(-1) and D2-260 CPUs)
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Conversion Settling Time
5µs maximum (full scale change)
Full Scale Calibration Error
(offset error included)
±12 counts max. unipolar @ 77ºF (25ºC)
±16 counts max. bipolar @ 77ºF (25ºC)
Offset Calibration Error
±3 counts max., unipolar @ 77ºF (25ºC)
±8 counts max., bipolar @ 77ºF (25ºC)
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.3% unipolar ranges @ 77ºF (25ºC)
±0.45% unipolar ranges >77ºF (25ºC)
±0.4% bipolar ranges @77ºF (25ºC)
±0.55% bipolar ranges >77ºF (25ºC)
Base Power Required 5VDC
40 mA
External Power Supply
18 to 30 VDC, 60 mA (outputs fully loaded)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
F2-02DA-2 2-Channel Voltage Analog Output Module
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).

Table of Contents