EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - Output Module

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–76
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD4DA-2 8-Channel Analog Voltage Input / 4-Channel Analog Voltage
Output Module
Output Channels per Module
4
Output Range
0 - 5V, 0 - 10V
Resolution
0 to 5V at 15-bit, 0 to10V at 16-bit, 152 µV/bit
Output Type
Voltage sourcing/sinking at 10 mA max.
Load Impedance
>1000
Max. Inaccuracy
0.15% of range
Max. Full Scale Calibration
Error (not incl. offset error)
±0.075% of range max.
Max. Offset Calibration Error
±0.025% of range max.
Accuracy vs. Temperature
±50 ppm/ °C max. full scale calibration change
(± 0.005% of range / °C)
Max. Crosstalk
@ DC, 50/60Hz
-70 dB, 1 LSB
Input Channels per Module
8, single ended (one common)
Input Range
0 to 10 V
Resolution
12, 14, 16-bit selectable
External DC Power Required
80 mA @ 18-26.4 VDC
Max. Continuous Overload
±100 V
Input Impedance
>10 M
Filter Characteristics
Active low pass, -3 dB @ 80Hz
Conversion Time
12-bit = 1.5 ms per channel
14-bit = 6 ms per channel
16-bit = 25 ms per channel
Conversion Method
Over sampling successive approximation
Accuracy vs. Temperature
±50 ppm / °C Max.
Maximim Inaccuracy
0.1% of range
Linearity Error (End to End)
12-bit = ±1 count max. (±0.025% of range)
14-bit = ±4 count max. (±0.025% of range)
16-bit = ±16 count max. (±0.025% of range)
Monotonic with no missing codes
Full Scale Calibration Error
(not including offset error)
±0.075% of range max.
Offset Calibration Error
±0.025% of range max.
Base Power Required 5VDC
35 mA

Table of Contents