EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - DL205 Combination Analog I;O Modules

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Combination Analog I/O Modules
DL205 Installation and I/O Manual, 2nd Edition
3–72
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04AD2DA 4-Channel Analog Input / 2-Channel Analog Output Module
Number of Input Channels
4, single-ended (1 common)
Number of Output Channels
2, single-ended (1 common)
Ranges
4 to 20 mA current (current sinking)
Resolution
12 bit (1 in 4096)
Peak Withstanding Voltage
75 VDC, current outputs
Max. Continuous Overload
-40 to +40 mA, each current output
Input Impedance
250 , ±0.1%, 1/2 W,
25 ppm/ºC current input resistance
External Load Resistance
0 minimum, current outputs
Maximum Loop Supply
30 VDC
Recommended Fuse
0.032 A, series 217 fast-acting, current inputs
Maximum Load/Power
Supply
910 /24 V, current outputs
620 /18 V, 1200 /30 V
Active Low-pass Filter
-3 dB @ 20 Hz, 2 poles (-12 dB per octave)
Linearity Error (best fit)
±1 count (±0.025% of full scale) maximum
Output Settling Time
100 µs maximum (full scale change)
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change)
Maximum Inaccuracy
±0.1% @ 77ºF (25ºC)
±0.3% @ 32 to 140ºF (0 to 60ºC)
Digital Input and Output
Points Required
16 (X) input points (12 binary data bits,
2 channel ID bits, 2 diagnostic bits)
16 (Y) output points (12 binary data bits,
2 channel enable bits)
PLC Update Rate
4 channels per scan maximum:
(D2-240, D2-250(-1) and D2-260 CPUs)
2 output channels per scan maximum:
(D2-240, D2-250(-1) and D2-260 CPUs)
1 input and 1 output channel per scan maximum:
(D2-230 CPU)
Base Power Required 5VDC
90 mA
External Power Supply
Requirement
18-26.4 VDC @ 80 mA
20 mA per loop
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
One count in the specification
table is equal to one least
significant bit of the analog
data value (1 in 4096).

Table of Contents