EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - D2-04 TD1, DC Output; DL205 Digital Output Modules

AutomationDirect D2-16ND3-2
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Digital Output Modules
D2-04TD1, DC Output
Outputs per Module
4 (current sinking)
Output Points Consumed
8 points (only first 4 pts. used)
Commons per Module
1 (4 I/O terminal points)
Output Type
NMOS FET (open drain)
Operating Voltage
10.2-26.4 VDC
Peak Voltage
40 VDC
ON Voltage Drop
0.72 VDC maximum
AC Frequency
N/A
Max Load Current
(resistive)
4A/point
8A/common
Max Leakage Current
0.1 mA @ 40 VDC
Max Inrush Current
6A for 100 ms, 15A for 10 ms
Minimum Load Current
50 mA
External DC Required
24 VDC @ 20 mA max.
Base Power Required 5VDC
60 mA
OFF to ON Response
1 ms
ON to OFF Response
1 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.8 oz. (80 g)
Fuses
4 (1 per point)
(6.3 A slow blow, non-replaceable)
0
1
2
3
4
0
10 20 30 40 50 55
Ambient Temperature (˚CF )
32 50 68 86 104 122 131
C˚
F˚
Points
2A / Pt.
3A / Pt.
4A / Pt.
0V
24V
C
C
C
C
0
1
2
3
24VDC
Internally
connected
L
L
L
L
+
12--24VDC
+
C
+24V
0
C
1
C
2
C
3
10.2--26.4VDC
50mA-- 4A
D2--04T D1
OUT 1 2 -- 2 4
D2--04TD1
VDC
0
1
2
3
L
L
L
L
C
Common
L
12--24
+
--
+--
24VDC
VDC
To LE D
Optical
Is olator
0V
Output
Othe r
Circuits
Reg
Inductive Load
0.1A 1400 600
0.5A 300 120
1.0A 140 60
1.5A 90 35
2.0A 70 --
Load
8000
1600
100ms
800
540
3.0A
400
270 -- --
40ms7msCurrent
Duration of output in ON s tate
4.0A 200
-- --
Maximum Number of Switching Cycles per Minute
6.3A
Dera ting C ha rt
At 40 mS duration, loads of 3.0A or greater cannot be used.
At 100 mS duration, loads of 2.0A or greater cannot be used.
Find the load current you expect to use and the duration that the
output is ON. The number at the intersection of the row and column
represents the switching cycles per minute. For example, a 1A
inductive load that is on for 100 ms can be switched on and off a
maximum of 60 times per minute. To convert this to duty cycle
percentage use: (duration x cycles)/60. In this example,
(60 x .1)/60 = .1, or 10% duty cycle.
Chapter 3: I/O Wiring and Specifications
3–28
DL205 Installation and I/O Manual, 2nd Edition
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D

Table of Contents