EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - Output Module

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–74
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD4DA-1 8-Channel Analog Current Input / 4-Channel Analog Current
Output Module
Input Channels per Module
8, single ended (one common)
Input Range
0 to 20 mA
Resolution
12, 14, 16-bit selectable
External DC Power Required
100 mA @ 18-26.4 VDC
Max. Continuous Overload
±45 mA
Input Impedance
100 0.1% 1/4W
Filter Characteristics
Active low pass, -3dB @ 80 Hz
Conversion Time
12-bit = 1.5 ms per channel
14-bit = 6 ms per channel
16-bit = 25 ms per channel
Conversion Method
Over sampling successive approximation
Accuracy vs. Temperature
±25 ppm / °C Max.
Maximum Inaccuracy
0.1% of range
Linearity Error
(End to End)
12-bit = ±2 count max. (±0.06% of range)
14-bit = ±10 count max. (±0.06% of range)
16-bit = ±20 count max. (±0.06% of range)
Monotonic with no missing codes
Full Scale Calibration Error
(not including offset error)
±0.07% of range max.
Offset Calibration Error
±0.03% of range max.
Rec. Fuse (external)
0.032A, Littelfuse Series 217 fast-acting
Base Power Required 5VDC
35 mA
Output Channels per Module
4
Output Range
4 to 20 mA
Resolution
16-bit, 0.244 mA/bit
Output Type
Current sourcing at 20 mA max.
Load Impedance
0-750
Max. Inaccuracy
0.25% of range
Max. Full Scale Calibration
Error (not incl. offset error)
±0.075% of range max.
Max. Offset Calibration Error
±0.1% of range max.
Accuracy vs. Temperature
±25 ppm/ °C max. full scale calibration change
(± 0.0025% of range / °C)
Max. Crosstalk at DC,
50/60Hz
-70 dB, 1 LSB
NOT SUPPORTED BY D2-230 AND D2-240 CPUs.

Table of Contents