EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - Page 107

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–75
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD4DA-1 8-Channel Analog Current Input / 4-Channel Analog Current
Output
shield, Channel 3
CH1 ADC
CH2 ADC
CH4 ADC
CH3 ADC
CH6 ADC
IN / ANALOG
F2-8AD4DA--1
0V
OUT2
OUT3
0V
IN2
IN3
0V
IN6
IN7
24V
OUT1
0V
OUT4
IN1
0V
IN4
IN5
IN8
0V
18--26.4VDC
8IN0--20mA
ANALOG
@ 100 mA
4OUT4--20mA
OUT
AC or DC
4--20mA transmitter
shield, Channel 8
transmitter
4--wire 4--20mA
SeeNote2
CH8 ADC
→ I8+
100Ω
100Ω
CH7 ADC
COM
0.032A
4--20mA transmitter
shield, Channel 5
transmitter
2--wire 4--20mA
→ I5+
Isolated analog
circuit common
4--20mA transmitter
transmitter
3--wire 4--20mA
COM
+
100Ω
→ I3+
100Ω
100Ω
100Ω
CH5 ADC
COM
Note 1: A Littlefuse Series 217, 0.032A fast--acting fuse is recommended for all 4--20mA current loop inputs.
Note 2: Connect shields to the 0V of the module; do not connect both ends of shield.
100Ω
100Ω
CH1 DAC
CH2 DAC
COM
CH4 DAC
CH3 DAC
Isolated analog
circuit power
User 24VDC
supply
COM
24VDC+
0VDC--
← I1+
← I2+
← I3+
← I4+
4--20mA output
Channel 2
--
4--20mA output
Channel 3
--
4--20mA output
Channel 4
--
4--20mA output
Channel 1
--
SeeNote2
Internal module wiring
Transmitter power
SeeNote1
+
+
+
+
SeeNote2
SeeNote2
Linearity Error (End to End)
±1 count max. (±0.025% of full scale)
Monotonic with no missing codes
Output Stability
and Repeatability
±1 LSB after 10 min. warm-up typical
Output Ripple
0.005% of full scale
Output Settling Time
0.5 ms max., 5 µs min. (full scale change)
Max. Continuous Overload
Outputs open circuit protected
Type of Output Protection
Electronically current limited to 20 mA or
less
Output Signal at
Power-up and Power-down
4 mA
Terminal Type (included)
Removable; D2-16IOCON

Table of Contents