EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - F2-08 DA-2 8-Channel Voltage Analog Output Module

AutomationDirect D2-16ND3-2
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–70
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08DA-2 8-Channel Voltage Analog Output Module
Number of Channels
8, single-ended, 1 common
Output Ranges
0 to 5V, 0 to 10V
Resolution
12 bit (1 in 4096)
Output Type
Voltage sourcing
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 3 channel ID bits,
1 output enable bit)
Base Power Required 5VDC
60 mA
External Power Supply
21.6-26.4 VDC, 140 mA (outputs fully loaded)
Peak Output Voltage
15 VDC
(clamped by transient voltage suppressor)
Load Impedance
1-10 k
Load Capacitance
0.01 µF maximum
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Conversion Settling Time
400 µs maximum (full scale change)
4.5 ms to 9ms for digital out to analog out
Linearity Error (end to end)
±1 count (±0.025% of full scale) maximum
Full Scale Calibration Error
±12 counts max. unipolar @ 25ºC (77ºF)
Offset Calibration Error
±3 counts max., unipolar @ 25ºC (77ºF)
Accuracy vs. Temperature
±57 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
±0.3% @ 25ºC (77ºF)
±0.45% @ 0-60ºC (32-140ºF)
Operating Temperature
0º to 60ºC (32º to 140°F)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).