EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - DL205 RTD and Thermocouple Modules

AutomationDirect D2-16ND3-2
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 RTD and Thermocouple Modules
DL205 Installation and I/O Manual, 2nd Edition
3–52
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04RTD 4-Channel RTD Input Module
Number of Channels
4
Input Ranges
Type Pt100: -200.0/850.0ºC,
-328/1562ºF
Type Pt1000: -200.0/595.0ºC,
-328/1103ºF
Type jPt100: -38.0/450.0ºC,
-36/842ºF
Type CU-10/25ž: -200.0/260.0ºC,
-328/500ºF
Resolution
16 bit (1 in 65535)
Display Resolution
±0.1ºC, ±0.1ºF (±3276.7)
RTD Excitation Current
200 µA
Input Type
Differential
Notch Filter
>100 db notches at 50/60 Hz
-3db=13.1Hz
Maximum Setting Time
100ms (full-scale step input)
Common Mode Range
0-5 VDC
Absolute Maximum
Ratings
Fault protected inputs to ±50 VDC
Sampling Rate
160 ms per channel
Converter Type
Charge Balancing
Linearity Error
±.05ºC maximum, ±.01ºC typical
Maximum Inaccuracy
±1ºC
PLC Update Rate
4 channel/scan max., 240/250(-1)/D2-260CPUs
1 channel per scan max., 230 CPU
Digital Input Points Required
32 input points (16 binary data bits,
2 channel ID bits, 4 fault bits)
Base Power Required 5VDC
90 mA
Operating Temperature
32° to 140°F (0° to 60°C)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Temperature Drift
None (self-calibrating)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON