D2-08NA-1, AC Input
Optical
COM
Is olator
INPUT
110 VAC
V+
To L E D
Internal module circuitry
COM
C
C
0
1
2
3
4
5
6
7
Internally
connected
110 VAC
0
2
4
6
8
0
10 20 30 40 50 55
Ambient Temperature (˚C/˚F)
32
50 68 86 104 122 131
C˚
F˚
Points
C
C
0
4
1
5
2
6
3
7
80-132VAC
10-20mA
D2--08NA-1
IN 110
D2--08NA --1
VAC
0
1
2
3
4
5
6
7
50/60Hz
Line
Dera ting Chart
Inputs per Module
8
Commons per Module
1 (2 I/O terminal points)
Input Voltage Range
80-132 VAC
Peak Voltage
132 VAC
ON Voltage Level
75 VAC minimum
OFF Voltage Level
20 VAC maximum
AC Frequency
47-63 Hz
Input Impedance
12 k@ 60 Hz
Input Current
13 mA @ 100 VAC, 60 Hz
11 mA @ 100 VAC, 50 Hz
Minimum ON Current
5 mA
Maximum OFF Current
2 mA
Base Power Required 5VDC
50 mA
OFF to ON Response
5 to 30 ms
ON to OFF Response
10 to 50 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.5 oz. (70 g)