To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–77
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD4DA-2 8-Channel Analog Voltage Input / 4-Channel Analog Voltage
Output
shield, Channel 3
CH1 ADC
CH2 ADC
CH4 ADC
CH3 ADC
CH6 ADC
IN / ANALOG
F2-8AD4DA--2
0V
OUT2
OUT3
0V
IN2
IN3
0V
IN6
IN7
24V
OUT1
0V
OUT4
IN1
0V
IN4
IN5
IN8
0V
18--26.4V
4OUTPUTS
0--10V
8INPUTS
0--5/0--10V
OUT
AC or DC
Voltage transmitter
shield, Channel 8
transmitter
4--wire voltage
SeeNote1
CH8 ADC
V8+
CH7 ADC
COM
Voltage transmitter
shield, Channel 5
transmitter
2--wire voltage
V5+
Isolated analog
circuit common
Voltage transmitter
transmitter
3--wire voltage
COM
+
V3+
CH5 ADC
COM
Note 1: Connect shields to the 0V of the module; do not connect both ends of shield.
CH1 DAC
CH2 DAC
COM
CH4 DAC
CH3 DAC
Isolated analog
circuit power
User 24VDC
supply
COM
24VDC+
0VDC--
V1+
V2+
V3+
V4+
Voltage output
Channel 2
--
Voltage output
Channel 3
--
Voltage output
Channel 4
--
Voltage output
Channel 1
--
SeeNote1
Internal module wiring
Transmitter power
+
+
+
+
SeeNote1
SeeNote1
80mA
Linearity Error (End to End)
±1 count max. (±0.025% of full scale)
Monotonic with no missing codes
Output Stability and
Repeatability
±1 LSB after 10 min. warm-up typical
Output Ripple
0.005% of full scale
Output Settling Time
0.5 ms max., 5µs min. (full scale change)
Max. Continuous Overload
Outputs current limited to 15 mA typical
Type of Output Protection
1 VDC peak output voltage
(clamped by transient voltage suppressor)
Output Signal at
Power-up and Power-down
0V
Terminal Type (included)
Removable; D2-16IOCON