F2-04AD-1 4-Channel 4-20mA Analog Input
Note 1: Shields should be grounded at the signal source
More than one external power supply can be used provided all the power supply commons are connected. A Series 217, 0.032A, fast-acting
fuse is recommended for
4-20 mA current loops. If the power supply common of an external power supply is not connected to 0VDC on the module, then the output of
the external transmitter
must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types are:
2 or 3 wire: Isolation between input signal and power supply.
4 wire: Isolation between input signal, power supply, and 4-20 mA output