F2-04THM 4-Channel Thermocouple Input
Input Ranges
Type J -190 to 760ºC -310 to 1400ºF
Type E -210 to 1000ºC -346 to 1832ºF
Type K -150 to 1372ºC -238 to 2502ºF
Type R 65 to 1768ºC 149 to 3214ºF
Type S 65 to 1768ºC 149 to 3214ºF
Type T -230 to 400ºC -382 to 752ºF
Type B 529 to 1820ºC 984 to 3308ºF
Type N -70 to 1300ºC -94 to 2372ºF
Type C 65 to 2320ºC 149 to 4208ºF
Display Resolution
±0.1ºC or ±0.1ºF
Cold Junction Compensation
Automatic
Conversion Time
100 ms per channel
Warm-Up Time
30 minutes typically ± 1ºC repeatability
Linearity Error (End to End)
±.05ºC maximum, ±.01ºC typical
Maximum Inaccuracy
±3ºC (excluding thermocouple error)
Voltage Input Specifications
Voltage Ranges
0-5V, ±5V, 0-156.25 mV, ±156.25 mVDC
Resolution
16 bit (1 in 65535)
Full Scale Calibration Error
(Offset Error Included)
±13 counts typical ±33 maximum
Offset Calibration Error
±1 count maximum, @ 0V input
Linearity Error (End to End)
±1 count maximum
Maximum Inaccuracy
±.02% @ 25ºC (77ºF)