EasyManua.ls Logo

AutomationDirect D2-16ND3-2 - Page 89

AutomationDirect D2-16ND3-2
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Installation and I/O Manual, 2nd Edition
3–57
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
OV
+--
24 VDC
See
0VDC
+24 VDC
N/C
N/C
N/C
N/C
NOTE 1
60mA
+24V
CH1--
CH1+
CH2--
CH2+
NC
NC
NC
NC
18--30VDC
60mA
F 2 -- 0 2 D A -- 1
OUT ANALOG
F 2 -- 0 2 D A -- 1
2CH
ANALOG OUT
4-- 20mA
0V
CH1--
CH2--
CH1+
CH2+
Current sinking
Ch 1
Current sinking
Ch 2
DC to DC
Converter
+5V
+15V
0V
-- 1 5 V
DtoA
Converter
DtoA
Converter
Ch 1 load
250Ω typical
Ch 2 load
250Ω typical
Internal
Module
Wiring
Transient protected
precision digital to analog
converter output circuits
Typical user wiring
NOTE 1: Shields should be connected to the 0V of the module or the OV of the R/S.
NOTE 2: Unused current outputs should remain open (no connections) for minimum power consumption.
F2-02DA-1 2-Channel 4-20mA Analog Output

Table of Contents