DL205 Installation and I/O Manual, 2nd Edition
3–59
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-02DA-1L 2-Channel 4-20mA Analog Output
OV
+--
12 VDC
See
0VDC
+12 VDC
N/ C
N/ C
N/ C
N/ C
NOTE 1
70mA + 20mA
for each loop
+V
CH1--
CH1+
CH2--
CH2+
NC
NC
NC
NC
10--15 VDC
70mA
F2--02DA--1L
OUT A NA LOG
F2--02DA--1L
2CH
ANALOG OUT
4--20mA
0V
CH1--
CH2--
CH1+
CH2+
Current sinking
Ch 1
Current sinking
Ch 2
DC to DC
Converter
+5V
+15V
0V
--15V
DtoA
Converter
DtoA
Converter
12
Ch 1 load
250Ω typical
Ch 2 load
250Ω typical
Internal
Module
Wiring
Transient protected
precision digital to analog
converter output circuits
Typical User Wiring
Maximum user load is dependent upon loop power supply.
Loop power supply Load range (ohm)
15 VDC 0 to 450
12 VDC 0 to 300
10 VDC 0 to 200
NOTE 1: Shields should be connected to the 0V of the module or the OV of the P/S.
NOTE 2: Unused current outputs should remain open (no connections) for minimum power consumption.