DL205 Installation and I/O Manual, 2nd Edition
3–61
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-02DAS-1 2-Channel Isolated 4-20mA Analog Output
Internal module
wiring
+
--
Trans mitter
See
0V1
+V1
0V2
-- I 2
+I2
+V2
NOTE 1
+V1
-- I 1
+I1
N/C
N/C
0V2
+V2
-- I 2
+I2
4--20mA
18-- 32VDC
F 2 -- 0 2 D A S -- 1
OUT A NA L OG
F2--02DAS --1
2CH
0V1
-- I 1
N/ C
+I1
N/ C
Ch 1 load
0--1375 ohms
NOTE 2
Supply
18--32VDC
See
NOTE 1
Ch 2 load
0--1375 ohms
NOTE 2
D/A
4--20mA current s ourcing
D/A
4--20mA current s ourcing
ANALOG OUT
100 ohms
100 ohms
NOTE 3
See
+
--
Trans mitter
S upply
18--32VDC
Typical user wiring
ONOTE 1: Shields should be connected to the 0V terminal of the module.
NOTE 2: Load must be within compliance voltage.
NOTE 3: For non-isolated outputs, connect all 0V’s together (0V1…0V2) and connect all +V’s together (+V1…+V2).