6 Timer mode 
© Copyright Reserved Autonics Co., Ltd.    69 
 
Time chart 
FLK 
[FLK] 
Flicker (Power RESET) 
1)Time starts when INA signal turns ON. 
2)When INA signal is ON: Power ON Time Start is 
 
  operated. RESET OFF Time Start is operated. 
3)Control output operates as retained output, output turns 
  off for the T.off time and turns off for the T.off time and 
  turns on for the T.on time repeatedly. 
  Ta+Tb = T.off 
4)The T.on time and T.off time must be set individually. 
5)In case of using the contact output, min. setting time must 
 
  be set over 100ms. 
 
FLK.1 
[FLk1] 
Flicker 1 (Power RESET) 
Retained(Hold) output 
1)Time starts when INA signal turns ON. 
2)When INA signal is ON 
 : Power ON Time Start is operated.   
 RESET OFF Time Start is operated. 
3)Control output operates as retained (Hold) output. 
4)In case of using the contact output, min. setting time must 
 
  be set over 100ms. 
 
※Power RESET: There is no memory protection. (resets the display value when power is off) 
※Power Hold: There is memory protection. (memorizes the display value at the moment of 
    power off, indicates the memorized display value when power is resupplied.)