[MODE] 2
Parameter 1
[MODE] 4
Parameter 2
[MODE]
Parameter 0
Zero adjustment
Auto
5
Reset
[MODE]
Parameter Defaults
condition
1-1 Input type
DCAC DC DC, -DC, AC -
1-2
Input
01)
IN-R
50)0
• Refer to Input Range and Display Range
1-1
Input
type
:
DC, AC
-50)0
1-1
Input
type
: -DC
%000
• Refer to Input Range and Display Range
1-1
Input
type
:
DC, AC
-%000
1-1
Input
type
: -DC
method
DISP STND
STND:
standard
, SCAL:
scale
,
FREQ: frequency
*, PF: power factor**
*1-1 Input
type: AC
**1-1 Input
type: ±DC
1-4
method
IN-T RMS
1-1
Input
type
: AC
1-5
High-limit
display value
gradient
correction
SPAN !000 0.100 to 9.999 %
method
:
STND
Low-limit
display value
deviation
correction
ZERO 00 -99 to 99
1-7
position
DOT
00)0
[DC / AC voltage model]
0, 0.0, 0.00, 0.000
method
:
SCAL
&
* 1-7
Decimal
point
position:
0.0, 0.00,
0.000
)000
[DC / AC current model]
0, 0.0, 0.00, 0.000
1-8
H-SC -
Display value against max. measurement input*
1-9
L-SC -
Display value against min. measurement input*
1-10
High-limit
display value
gradient
correction
SPAN !000 0.100 to 9.999 %
1-11
Low-limit
display value
deviation
correction
02)
ZERO 00 -99 to 99
1-12
position
DOT
00)0
[DC / AC voltage model]
0, 0.0, 0.00, 0.000
method
:
FREQ
)000
[DC / AC current model]
0, 0.0, 0.00, 0.000
High-limit
display value
gradient
correction
SPAN !000 0.100 to 9.999
1-14
Exponent of
SPAN
eSPN 10-0
10-0: 10
0
, 10-1: 10
-1
, 10-2: 10
-2
, 10 1: 10
1
1-15
H-RG - Max. value of input range
method
:
PF
L-RG - Min. value of input range
1-17
Display unit dUNT
V
[DC / AC voltage model]
V, MV, OFF
-
A
[DC / AC current model]
A, MA, HZ, OFF
When changing input range, the following parameters are reset.
- Parameter 1 group: display method, measurement method, decimal point position, high / low-limit scale, high-limit
display value gradient correction, exponent of span, high / low-limit input value, display unit
- Parameter 2 group: OUT1 / 2 output operation mode, OUT1 / 2 hysteresis
- Parameter 0 group: OUT1 / 2 high-limit output setting value, OUT1 / 2 low-limit output setting value, max. / min. peak value
Low-limit display value deviation correction range is within -99 to 99 for D
0
, D
-1
digit regardless of decimal point position.
Display range is variable according to decimal point position.
Dot Frequency
0 -9999 to 9999 1 to 1200 Hz
)0 -999.9 to 999.9 0.1 to 999.9 Hz
)00 -99.99 to 99.99 0.10 to 99.99 Hz
)000 -9.999 to 9.999 0.100 to 9.999 Hz
Parameter Defaults
condition
2-1
OUT1
mode
OU!T OFF
[Preset output model]
-
2-2
OUT2
mode
OU@T OFF
[Preset output model]
-
hysteresis
HYs1
0)1
[DC / AC voltage model]
Within 10 % of max. display range, digit
2-1 OUT1
mode:
except
OFF
)001
[DC / AC current model]
Within 10 % of max. display range, digit
2-4
OUT2
hysteresis
HYs2
0)1
[DC / AC voltage model]
Within 10 % of max. display range, digit
2-2 OUT2
mode:
OFF
)001
[DC / AC current model]
Within 10 % of max. display range, digit
2-5
Startup
compensation
time
STaT 0)0 00.0 to 99.9 sec -
Peak
monitoring
delay time
PEaK 00 S -
2-7 DIsT )2 S 0.2 to 5.0 sec -
2-8
terminal
DI-T HOLD
[Preset output model]
HOLD, ZERO
-
2-9 Lock LOC OFF
OFF: unlock,
LOC1: ,
LOC2: ,
-
Parameter Defaults
condition
0-1
OU!H
50)0 [DC / AC voltage & preset output model]
2-1 OUT1
mode:
%000 [DC / AC current & preset output model]
0-2
OU!L
00)0 [DC / AC voltage & preset output model]
1-1 Input
type:
DC, AC
&
2-1 OUT1
mode:
LOW, HL,
)000 [DC / AC current & preset output model]
-50)0 [DC / AC voltage & preset output model]
1-1 Input
type: -DC
&
2-1 OUT1
mode:
LOW, HL,
-%000 [DC / AC current & preset output model]
OU@H
50)0 [DC / AC voltage & preset output model]
2-2 OUT2
mode:
%000 [DC / AC current & preset output model]
0-4
OU@L
00)0 [DC / AC voltage & preset output model]
1-1 Input
type:
DC, AC
&
2-2 OUT2
mode:
LOW, HL,
)000 [DC / AC current & preset output model]
-50)0 [DC / AC voltage & preset output model]
1-1 Input
type: -DC
&
2-2 OUT2
mode:
LOW, HL,
-%000 [DC / AC current & preset output model]
0-5
02)
hPEK )0 Max. peak value in run mode
2-1 OUT1
mode:
except
OFF
or
2-2 OUT2
mode:
except
OFF
&
monitor-
ing delay
time:
except
00
lPEK )0 Min. peak value in run mode