I-50
SPC1 Series
Specications
Features
Single-Phase, Power Controller
● Various and simple input specication
• DC4-20mA, 1-5VDC, External 24VDC
• External adjuster (1kΩ)
• External contact (ON/OFF)
● Various function
• OUT ADJ (output limit) function
•
SOFT START function (except for ON/OFF control method)
• OUT display function
• 50/60Hz automatic converting function
● Various control method by switch
• Phase control method
• Cycle control method (zero cross turn-on)
• ON/OFF control method (zero cross turn-on)
Ordering Information
Rated load current
Marking language
Item
SPC 35 E1 - -
35 35A
50 50A
E English
1 Single-phase
SPC Solid state power controller
Control phase
Model
SPC1-35-E SPC1-50-E
Power supply 220VAC
ᜠ
50/60
Hz
Allowable voltage range 90 to 110% of rated voltage
Operating frequency uctuation
±1Hz
Rated load current 35A (single-phase) 50A (single-phase)
Control power 220VAC
ᜠ
Control range Phase control: 0 to 98%, Cycle control: 0 to 100%
Applied load Resistance load (min. load: over 5% of rated current)
Cooling method Natural cooling
Control circuit Micom control type
Control input
• 1-5VDC
ᜡ
• DC4-20mA (250Ω) • ON/OFF (external relay contact or 24VDC
ᜡ
)
• External adjuster (1kΩ) • Output limit input (front OUT ADJ. adjuster)
Control
method
By selection
switch
• Phase control
※
1
• Cycle control (zero cross turn-on) - Period 0.5 sec, 2.0 sec, 10 sec
※
1
• ON/OFF control (zero cross turn-on)
Starting type SOFT START (0 to 50 sec variable)
Indicator Output indicator (OUT): red LED
Insulation resistance Over 100MΩ (at 500VDC megger)
Dielectric strength 2000VAC 50/60Hz for 1minute
Noise immunity ±2kV the square wave noise (pulse width: 1us) by the noise simulator
Vibration
Mechanical
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Malfunction
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Shock
Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Malfunction 100m/s² (approx. 10G) in each X, Y, Z direction for 3 times
Environment
Ambient temp. 0 to 50
℃
, storage: -25 to 65
℃
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Wire specication
AWG16 to 8
AWG8 to 6
Unit weight Approx. 1kg
※
1:
Refer to '
Operation and Function
'.
※
Environment resistance is rated at no freezing or condensation.
Please read “Safety considerations” in operation
manual before using.
SPC1 Series