1 Modbus RTU Protocol
© Copyright Reserved Autonics Co., Ltd. 17
1.7 Preset multiple registers(Func 16–10H)
Write the Binary data of Holding Registers (4X reference) consecutively in Slave device.
(1) Query (Master)
Slave
Address
Function
No. of register
Byte count
Data Data
1Byte 1Byte 1Byte 1Byte
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
1Byte
1Byte 1Byte
(2) Response (Slave)
Slave address Function
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
If write “10(A H)” in common to the range of Holding Register 400001(0000 H) to 400002(0001
H) on Slave from Master.
Query (Master)
Slave
address
Function
No. of register
Byte count
Data Data
11 H 10 H 00 H 00 H 00 H 02 H 04 H 00 H 0A H 00 H 0A H ## H ## H
Response (Slave)
Slave address Function
11 H 10 H 00 H 00 H 00 H 02 H ## H ## H
Please use the Single Register Write function rather than Multi Register Write function if you use
the slave(device) connecting with external devices such as PLC, Graphic Panel, except in the
case of download that presets the minimum/maximum or basic value of parameter by Input
specifications in PC Loader Program