2 Modbus Mapping Table
30 © Copyright Reserved Autonics Co., Ltd.
2.5.6 Communication setting group(Func: 03/06/16, RW: R/W)
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
4
00601(0258)
4
00301(012C)
Ba
udrate
Communication
s
peed
0: 2400 1: 4800
2: 9600 3: 19200
4: 38400
-
2
4
00602(0259)
4
00302(012D)
Parity Bit
Communication
p
arity bit
0: NONE 1: EVEN
2: ODD
-
0
4
00603(025A)
4
00303(012E)
Stop Bit
Communication
s
top bit
0: 1
1: 2
-
1
40
0604(025B)
4
00304(012F)
Response Waiting
Time
Response
w
aiting time
5
to 99
ms
20
4
00605(025C)
4
00305(0130)
Communication
Write
Communication
w
rite
0: ENABLE
1: DISABLE
-
0
4
00606(025D)
4
00306(0131)
Parameter Initializ
e
Parameter
i
nitialization
0: NO
1: YES
-
0
4
00607(025E)
to
4
00700(02BB)
4
00307(0132)
to
4
00350(015D)
Reserved

Other manuals for Autonics TM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TM Series and is the answer not in the manual?

Autonics TM Series Specifications

General IconGeneral
BrandAutonics
ModelTM Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals