2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd. 23
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
3
01027(0402)
-
CT1_Heater
Current
CT1
heater current value
m
onitoring
0.0
to 50.0
A
-
3
01028(0403)
-
CT2_Heater
Current
CT2
heater current value
m
onitoring
0.0
to 50.0
A
-
Consists of the 301025(0400) Address bit data
Bit F
Bit E
Bit D
Bit C
Bit B
Bit A
Bit 9
Bit 8
- - - - - - DI-2 input DI-1 input
0 0 0 0 0 0 0 or 1 0 or 1
1 Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
AL4 LED AL3 LED AL2 LED AL1 LED CH4 LED CH3 LED CH2 LED CH1 LED
0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1
1 Byte