EasyManuals Logo

Autonics TM Series User Manual For Communication

Autonics TM Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd. 27
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
4
00216(00D7)
4
00116(0073)
CH1
Ramp_Up
Rate
Ramp
up change
r
ate
0
(OFF) to 9999
//
Digit
0
4
00217(00D8)
4
00117(0074)
CH1 Ramp_Down
Rate
Ramp
down
c
hange rate
0
(OFF) to 9999
//
Digit
0
4
00218(00D9)
4
00118(0075)
CH1 Ramp Time
Unit
Ramp
time unit
0: SEC 1: MIN
2: HOUR
-
1
40
0219(00DA)
to
4
00300(012B)
40
0119
to
4
00150(0095)
CH1
reserved
4
01201(04B0)
to
4
01300(0513)
4
01101(044C)
to
4
01150(047D)
CH2
parameter - the same as above CH1
-
4
02101(0834)
to
4
02150(0865)
CH3
parameter - the same as above CH1
-
4
03101(0C 1C)
to
4
03150(0C4D)
CH4
parameter - the same as above CH1

Other manuals for Autonics TM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TM Series and is the answer not in the manual?

Autonics TM Series Specifications

General IconGeneral
BrandAutonics
ModelTM Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals