Cautions during use
Error Display
Troubleshooting
Symptoms Troubleshooting
OPEN
is displayed on
the PV display during
operation
Disconnect the power and check the input connection.
If the input is connected, disconnect the input wiring from the temperature controller and short the
+ and - terminals. Power the temperature controller and check if it displays the room temperature.
If it does not display the room temperature and continues to display
OPEN
, the controller is broken.
Please contact our technical support. (Input type is thermocouple)
Load (heater, etc.)
does not operate
during operation
Check the state of the control output indicator on the front panel.
If the indicator is not working, check parameter settings. If the indicator is working, disconnect the
wiring from the output terminal of the temperature controller and check the output (replay contact,
SSR drive, current).
ERR0
(error) is
displayed on the
PV display during
operation
Indicates damage to internal chip by strong noise (2kVAC).
Please contact our technical support. Locate the source of the noise and devise countermeasures.
Display Description Troubleshooting
OPEN
Blinks when input is disconnected. Check input status.
HHHH
Blinks when the measured input value is higher than the temperature range.
Adjust the value to within the
temperature range.
LLLL
Blinks when the measured input value is lower than the temperature range.
Proper Usage
Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
Check the polarity of the terminals before wiring the temperature sensor.
For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.
Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded
wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the
power.
Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
When changing the input sensor, turn off the power first before changing.
After changing the input sensor, specify internal switch and modify the value of the corresponding parameter.
Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect
of external noise.
Make a required space around the unit for radiation of heat.
For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
Do not wire to terminals which are not used.
This unit may be used in the following environments.
Indoors (in the environment condition rated in 'Specifications')
Altitude max. 2,000m
Pollution degree 2
Installation category II