Parameter Group
ON ON1
SU-2
AL1
AL2
LBA
AHYS
P
I
D
T
HYS
IN-B
REST
RAPU
RAPD
LOC
3 sec
3 sec
0
10
10
600
2
#0
0
0
20
2
0
)0
10
10
OFF
● Parameter group 1
2
1
RUN mode
Parameter setting order
Parameter group 2
Parameter group 1 SV setting
The parameters are related to each other. Please set the parameters in the order above.
When there is no key input for 60 sec while in SV setting mode or parameter groups, the unit will return to RUN mode
automatically.
SV setting Parameter group 1 Parameter group 2
+ 3 sec
RUN mode
3 sec
3 sec
3 sec
1: : ( )key-Switch elds, , key-Change values
2: Press the key after checking or changing the values in parameter settings to
save the setting value and move to the next parameter.
Hold the key for 3 sec anytime during parameter settings to save the setting
value and return to RUN mode.
The dotted line parameters may not appear depending on the model or other
parameter settings.
PV display SV display
SV 2
temperature
Event 1
alarm
temperature
Event 2
alarm
temperature
LBA
monitoring
time
Alarm
output
hysteresis
Proportional
band
Integral
time
Derivative
time
Control
period
Hysteresis
Input
correction
Manual
reset
Ramp
up time
Ramp
down time
Lock
OFF
Unlock
ON
Lock parameter 1 ( key available)
ON1
Lock parameter 1 ( key unavailable)
Setting range:
Setting range: refer to ' Input Type and Range'.
Setting range: refer to ' Input Type and Range'.
[
AL1
,
AL2
] parameters do not appear when Event 1/2 [
EU-1
,
EU-2
] of parameter
group 2 is set to
AL-0
,
LBA
,
SBA
.
[
AL2
] parameter only appears in models that support Event 2 output.
Setting range: 0 to 999 sec
Only appears when Event1/2 [
EU-1
,
EU-2
] of parameter group 2 is set to
LBA
.
Does not appear in current output models.
Setting range: 1 to 100
/
(0.1 to 100.0
/
)
Does not appear when Event 1/2 [
EU-1
,
EU-2
] of parameter
group 2 is set to
AL-0
,
LBA
,
SBA
.
Setting range: 0.0 to 100.0%
ON/OFF control: Set to
)0
, PID control: Set to over
)0
Only appears during PID
control (proportional band
[
P
] set to over
)0
).
Setting range: 1 to 100
/
(0.1 to 100.0
/
)
Only appears during ON/OFF control (proportional band [
P
] set to
)0
).
Setting range: -49 to 50
/
(-50.0 to 50.0
/
)
Setting range: 0.0 to 100%
Only appears when P control (proportional band [
P
] set to over
)0
, integral time [
I
],
and derivative time [
D
] are set to
0
)
Setting range: 1 to 99 min
Only appears when ramp function [
RAMP
] of parameter group
2 is set to
ON
.
Setting range: 0 to 3,600 sec
Integral operation is turned OFF when set to
0
.
Setting range: 0 to 3,600 sec
Derivative operation is turned OFF when set to
0
.
Setting range: 1 to 120 sec
Set to a small value in SSR drive output models. (e.g. 2 sec)
Does not appear in current output models.