Level II Parameters
The Level II parameters are P6 through P19 in Table 2.
The Home Owners Manual for this product does not
mention these parameters, so the end user does not
normally have access to these values. To access Level
II Parameters, simultaneously press and hold the down
arrow (↓) and up arrow (↑) button for three seconds.
If the control was alternating between Time of Day and
Capacity when the above button sequence is entered,
the display shows P1. If a different Level I Parameter
was displayed, the display, shows the “P” number for
that parameter. Refer to Table 2 to find the “P” number
associated with each parameter.
Use the up arrow (↑) button or the down arrow (↓)
button to move from one parameter to the next. The
display cycles through the “P” numbers shown in
Tables 1 and 2. When you reach P19, the display will go
back to P1.
When the parameter number you want to change is
displayed, press the left arrow (←) button to display the
data assigned to that parameter. Press the SET button
Table 2 - Level II Programming Parameters
Parameter
Range of
Values
Minimum
Increments
Default
Units of
Measure
Notes
Name Description
P6
Refill Control
Value
1 to 99 1 99
Set to 99 for 960F operation. Skip for
default.
P7
Brine draw
value
1 to 99 1 99 Set to 99 for 960F operation.
P8 Not used NA NA NA NA NA
P9
Backwash
time
3 to 30 1 14 Minutes
Enter the desired backwash time in
minutes. Skip for default.
P10
Slow Rinse
time
8 to 125 1 8 Minutes Set to 8 minutes for 960F operation.
P11
Fast Rinse
time
2 to 19 1 9 Minutes
Enter the desired fast rinse time in
minutes. Skip for default.
P12
Units of
measure
0 to1 1 0
0=U.S., 1=Metric. Skip this parameter
to accept U.S. or enter 1 for Metric.
P13 Clock mode 0 to 1 1 0
0=12-hour clock, 1=24-hour clock. Skip
this parameter for a 12-hour clock or
enter 1 for a 24-hour clock.
P14
Calendar
override
0 to 30 1 0 Days
0=no calendar override. Skip this
parameter for no calendar override or
enter a value.
P15 Reserve type 0 to 3 1 0
0=variable reserve, 1=fixed reserve,
2=variable reserve with immediate
backwash, 3=fixed reserve with
immediate backwash. Skip this
parameter to accept the default or enter
a different reserve type.
P16
Fixed reserve
capacity or
initial average
value
0 to 70 1 30
Percent of
capacity
Description depends on the value
entered for P15. Skip this parameter to
accept the default or enter a different
value.
P17
Operation
type
0 to 1 1 4 Set to 4 for 960F operation.
P18
Factor B/
Capacity
0 to 1 change
lock out
10
0=none, 1=Factor B/Capacity change
locked out. Skip this parameter to
accept the default or enter 1 to lock out
Factor B/capacity change.
P19
Factory
defaults
0 to 3 1 99
Loads in factory default values.
Do not change this parameter.