Temperature Specifications
Fresh air For information about fresh air, see Expanded Operating
Temperature section.
Maximum temperature gradient (operating
and storage)
20°C/h (68°F/h)
Table 2: Relative humidity
Relative humidity Specifications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating 10% to 80% relative humidity with 29°C (84.2°F)
maximum dew point.
Table 3: Maximum vibration
Maximum vibration Specifications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides
tested).
Table 4: Maximum shock
Maximum shock
Specifications
Operating Six consecutively executed shock pulses in the positive
and negative x, y, and z axes of 6 G for up to 11 ms.
Storage Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Table 5: Maximum altitude
Maximum altitude
Specifications
Operating 3048 m ( 10,000 ft)
Storage 12,000 m (39,370 ft)
Table 6: Operating temperature de-rating
Operating temperature de-rating
Specifications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547
ft) above 950 m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319
ft) above 950 m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228
ft) above 950 m (3,117 ft).
Environmental requirements
December 2018 Installing the Avaya Converged Platform 120 Series 15