Chapter 4. BASIC OPERATION
Note (Advanced use, direct setup function)
Control can be executed using an SP No. or SP value currently
being changed (indicated by blinking display) when the direct
setup function is enabled for the instantaneous flow rate direct
setup function ON/OFF (
C-2
1
in the function setup). In this
case, the [ENT] key need not be pressed to enter the SP value.
Handling Precautions
When switching the display by pressing the [DISP] key, first
press the [ENT] key to enter the SP value. For details on how to
set up functions,
Chapter 5. ADVANCED OPERATION.
Handling Precautions (Common to single setup and multi-setup)
When "1: Analog setup" is selected as the flow rate setup
method (
C-
03
in the function setup) and the SP value is con-
trolled by external voltage input, the SP value and SP No. can-
not be changed with the [
]or [] key.
If no operation is made for approximately 10 s after the opera-
tion stated in (1) has been performed, the display automati-
cally returns to the instantaneous flow rate display.
If the [DISP] key is pressed during the operations in steps (2)
and (3) (setting is blinking), the SP No. and SP value return to
their previous values without saving of new values.
When the SP value is updated in step (3) for single setup or
in step (4) for multi-setup, the display automatically returns
to the instantaneous flow rate display after approximately 2 s
have elapsed.