MODEL BPM 200 BPM 300 BPM 350 BPM 450
Maximum natural gas heat power
kW
210 307 350 415
Minimum natural gas heat power
kW
30 65 70 113
¹) natural gas emissions
mg/kWh
Class 3 Class 3 Class 3 Class 3
Operation
Modulating Modulating Modulating Modulating
50 Hz natural gas transformer
15kv - 25mA 15kv - 25mA 15kv - 25mA 15kv - 25mA
60 Hz natural gas transformer
15kv - 25mA
Maximum natural gas heat rate
Stm³/h
22.22 32.48 37 44
Minimum natural gas heat rate
Stm³/h
3.17 6.8 7.4 7.9
Maximum natural gas pressure
hPa
(mbar)
60 60 60 60
Minimum natural gas pressure
hPa
(mbar)
17 17 17 17
Maximum propane pressure
hPa
(mbar)
60 60
Minimum propane pressure
hPa
(mbar)
20 20
Absorbed electrical power* 50hz
kW
0.37 0.415 0.415 0.915
Absorbed electrical power* 60hz
kW
0.37 0.415 0.415 0.915
50 Hz power supply voltage
1N-230V 1N-230V 1N-230V 1N-230V
60 Hz power supply voltage
1N-230V 1N-230V 1N-230V 1N-230V
Protection rating
IP 20 IP 20 IP 20 IP 20
Control box
LME 71 LME 71 LME 71 LME 71
Operating ambient air temperature
°C
-15 ÷ +40 -15 ÷ +40 -15 ÷ +40 -15 ÷ +40
Sound power***
dBA
73 75
Weight with packaging
kg
28 28 37 45
Weight without packaging
kg
23 23 32 40
Unavailable
Caloric power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. ow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
¹) NATURAL GAS EMISSIONS
Classes dened according to EN 676 standards.
Class NOx emissions in mg/kWh natural gas
1 ≤ 170
2 ≤ 120
3 ≤ 80
²) PROPANE GAS EMISSIONS
Classes dened according to EN 676 standards.
Class NOx emissions in mg/kWh propane gas
1 ≤ 230
2 ≤ 180
3 ≤ 140