CONVERSION FROM NATURAL GAS TO
LPG
BPM 10 - 40 - 90
To t the nozzle, proceed as follows:
close the gas valve;
disconnect the gas valve (b) from the mixer unit (c) loosening the
four fastening screws;
t the nozzle for fuel LPG (d) inside the gasket (e);
assemble the components, making sure to correctly position the
sealing gaskets (e)
switch on the appliance once assembling is complete.
Upon ignition, carry out a leak test of the gas circuit and make sure
that oxygen values (O2%) at max. and min. power are within the tole-
rances shown in the table below.
CAUTION
Once the conversion has been carried out, apply the supplied
adhesive plate "GPL" (h) on the burner.
BPM 10 - 40 - 140 - 200 - 300
For LPG operation a specic fuel nozzle is not required, but only the
maximum pressure adjustment screw will be used, during the ignition
and adjustment phase.
BPM 350 - 450 - 500 - 650 - 800
LPG is not used for these models.