Operation Manual no. BP/IO/21/16 ed. 5.2.1
6 Technical parameters
Table 4: Technical parameters
Technical parameters
DC/AC input power 1 W/VA 50Hz
Rated DC/AC supply voltage 24/42 V
Permitted AC supply voltage 17…53 V
Permitted DC supply voltage 19…75 V
Contacts 2 change-over contacts
Relay mechanical strength 3 10
7
Rated load 250VAC 5A
120VAC 3A
240VAC 1,5A
30VDC 4A
120VDC 0,22A
250VDC 0,1A
AC1
AC15
AC15
DC1
DC13
DC13
Open contact insulation strength 1000 V AC/DC
Coil-to-contact insulation strength 5 kV
Ingress protection rating IP20
Measuring voltage 18 ± 5% V
Rated network voltage 1140 V AC
Rated frequency of the protected network 50 Hz
Settings range 2…120
Leakage stage tripping time (preferred connection layout, see Fig. 4a-
4d, with incremental change of leakage resistance from infinity to 1kΩ
ref. PN-G-42040)
100 ms
Leakage stage tripping time (preferred connection layout, see Fig. 4e-
4h, ref. PN-EN 50628)
200 ms
Additional time delay 0…1,5 s
Return value min. 30% above the response
threshold
Measuring output (analogue spark-proof)
1
0…10 V
1
at Ri
min
= 100kΩ