9287500995 Rev B 69
Generator Overvoltage Protection
Pickup
Range ......................................... 105 to 120% of setpoint
Increment ................................... 1.0%
Time Delay
Fixed Setting .............................. 0.75 seconds
Soft-Start Function
Time Adjust Range ..................... 1 to 120 seconds
Increment ................................... 1 second
Analog (Auxiliary) Input
Voltage Range ........................... –3 Vdc to +3 Vdc
Setpoint Range .......................... –30% to +30% shift
Burden ........................................ 1 kΩ
Terminals.................................... A, B
Metering
Accuracy of all metering values assumes 25°C, 50/60 Hz and less than 20% THD.
Generator Voltage
Range ......................................... 10 V to 79 kV
Accuracy..................................... 0.5%
Generator Current
Range ......................................... 0.1 to 5,000 A (5 A CTs)
Accuracy..................................... 0.5%
Frequency
Range ......................................... 40 to 65 Hz
Accuracy..................................... 0.2 Hz
Field Voltage
Range ......................................... 0 to 200 Vdc
Accuracy..................................... 5.0%
Field Current
Range ......................................... 0 to 8.0 Adc
Accuracy..................................... 0.5%
Power (Apparent, Real and Reactive)
Range ......................................... 0 to 99 MVA, MW and Mvar
Accuracy..................................... 3.0%
Power Factor
Range ......................................... –1.0 to –0.6, +0.6 to +1.0
Accuracy..................................... 0.02
Phase Angle
Range ......................................... 0 to 360°
Accuracy..................................... 2°
BE2000E Specifications