Commissioning
EL34xx 213Version: 1.5
Index F801 PMX Total Settings PQF
Index (hex) Name Meaning Data type Flags Default
F801:0 PMX Total Settings
PQF
Max. subindex UINT8 RO 0x13 (19
dec
)
F801:11 Nominal voltage A nominal voltage value or set value is required to
calculate the power quality factor (for details see ba-
sic function principles).
REAL32 RW 0x43660000
(1130758144
dec
)
F801:12 Nominal Frequency A nominal frequency or set value is required to calcu-
late the power quality factor (for details see basic
function principles).
REAL32 RW 0x42480000
(1112014848
dec
)
F801:13 PQF Dataset permitted values: UINT32 RW 0x00000001 (0
dec
)
0: default
1: default + unbalace

Table of Contents