Product description
EL690022 Version: 3.1.0
Product designation EL6900
Nitrogen dioxide: (1250 ± 20) ppb
Chlorine: (10 ± 5) ppb
Sulfur dioxide: (300 ± 20) ppb
Protection rating IP20
Device type according to EN
61010-2-201
Open equipment
Permitted operating environment In the control cabinet or terminal box, with minimum protection
rating IP54 according to IEC60529
Permissible installation position
see chapter Installation position and minimum distances [}25]
Approvals CE, cULus, ATEX, TÜV SÜD
1
A corrosive environment exists when corrosion damage becomes apparent.
4.4 Safety parameters
Key figures EL6900
Lifetime [a] 20
Prooftest Interval [a] not required
1
PFH
D
1.03E-09
%SIL3 1,03%
PFD 8.23E-05
%SIL3 8,23%
MTTF
d
high
DC high
Performance level PL e
Category 4
HFT 1
Element classification
2
Type B
1. Special proof tests are not required during the entire service life of the EL6900 EtherCAT terminal.
2. Classification according to IEC 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)
The EL6900 EtherCAT Terminal can be used for safety-related applications within the meaning of
IEC61508:2010 up to SIL3 and EN ISO 13849-1 up to PL e (Cat4).
For the calculation or estimation of the MTTF
d
value from the PFH
D
value, further information can be found in
the TwinSAFE application manual or in ISO 13849-1:2015 Table K.1.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff TwinSAFE EL6900 and is the answer not in the manual?

Beckhoff TwinSAFE EL6900 Specifications

General IconGeneral
BrandBeckhoff
ModelTwinSAFE EL6900
CategoryNetwork Hardware
LanguageEnglish

Related product manuals