Product description
EL6900 21Version: 3.1.0
4.3 Technical data
The current certificates of all TwinSAFE products with the underlying standards and directives can be found
at https://www.beckhoff.com/en-en/support/download-finder/certificates-approvals/.
Product designation EL6900
Number of inputs 0
Number of outputs 0
Status display 4 diagnostic LEDs
Minimum cycle time approx. 500µs
Fault reaction time ≤ watchdog times
Watchdog time Min. 2ms, max. 60000ms
Input process image Dynamic according to the TwinSAFE configuration in the TwinCAT
System Manager
Output process image Dynamic according to the TwinSAFE configuration in the TwinCAT
System Manager
EL6900 supply voltage (PELV) 24V
DC
(–15%/+20%)
Protection class III (by using a SELV/PELV power supply unit)
Overvoltage category II
Current consumption via E-bus approx. 188mA
Power loss of the terminal typically 1W
Dimensions (WxHxD) 12mm x 100mm x 68mm
Weight approx.50g
Permissible ambient temperature
(operation) up to SW 04
0°C ... +55°C (see chapter Example configuration for temperature
measurement [}26])
Permissible ambient temperature
(operation) from SW 05 (CW 02/2014)
-25°C ... +55°C (see chapter Example configuration for
temperature measurement [}26])
Permissible ambient temperature
(transport/storage)
-40°C ... +70°C
Permissible air humidity 5% to 95%, non-condensing
Permissible air pressure (operation/
storage/transport)
750hPa to 1100hPa (this is equivalent to an altitude of approx.
-690m to 2450m above sea level assuming an international
standard atmosphere)
Climate category according to
EN60721-3-3
3K3 (the deviation from 3K3 is only possible with optimal
environmental conditions and also applies only to the technical
data which are specified differently in this documentation)
Permissible degree of pollution
according to EN 60664-1
2 (see chapter Maintenance)
Inadmissible operating conditions TwinSAFE terminals must not be used under the following
operating conditions:
under the influence of ionizing radiation (exceeding the natural
background radiation)
in corrosive environments
1
in an environment that leads to unacceptable soiling of the bus
terminal
Vibration/shock resistance conforms to EN60068-2-6/ EN60068-2-27
EMC immunity/emission conforms to EN61000-6-2/ EN61000-6-4
Shocks 15g with pulse duration 11ms in all three axes
Corrosive gas test According to DINEN60068-2-60:2016-06, method 4 with
increased concentrations according to ANSI/ISA 71.04:2013 Level
GX Group A
Test duration: 21 days
Hydrogen sulfide: (50 ± 5) ppb

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff TwinSAFE EL6900 and is the answer not in the manual?

Beckhoff TwinSAFE EL6900 Specifications

General IconGeneral
BrandBeckhoff
ModelTwinSAFE EL6900
CategoryNetwork Hardware
LanguageEnglish

Related product manuals