5.2.1 Compensating Test Lead Resistance
TELARIS 0100 plus allows for compensation of test
lead resistance. The test lead resistance may
amount up to 1,99. Proceed as follows:
Connect 2 test leads to the TELARIS 0100 plus
(sockets L1 and L2). Connect any measurement
accessories used to measurement connections
L and N.
Short-circuit both test leads U+ and U-.
Set measurement range selection switch (32) to
„LOW-" measurement range.
Press „COMP" (22) key.
If the test lead resistance has been properly
compensated for, the symbol „COMP" (15) and
the value 0.00 Ohm appears on the display. Fur-
thermore, an acoustic signal is audible. If the
test lead resistance exceeds 1,99 Ohm, the
symbol „COMP" (15) blinks twice and the error
signal is audible.
The compensation value is maintained even
after switching the instrument off.
To clear the compensation value, please press
the "COMP” key (22) again.
12
Compensating Test Lead Resistance
RINS, Low
V
AC/DC