Data
38
RCM420_D00057_03_M_ XXEN/03.2021
6. Data
6.1 Factory setting
Response value overcurrent I1
(prewarning)
Response value overcurrent I2 (alarm)
Hysteresis
Fault memory M
Operating mode K1/K2
Starting delay
Response delay
Delay on release
Transformer correction factor n (n
RCM
)
Password:
15 mA (50 % of I2)
30 mA
15 %
activated (on)
N/C operation
(n.c.)
t = 0.5 s
t
on1
= 1 s
t
on2
= 0 s
t
off
= 1 s
1
0, deactivated
(Off)