EasyManua.ls Logo

Benning PV 3 - Technical Information; General, Environment, and Electrical Specifications

Benning PV 3
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01/ 2019
BENNING PV 3
16
reduced in order to allow the BENNING PV 3 to cool down. Do not leave the BENNING PV 3 attached to
a hazardous voltage for extended periods of time or while waiting for the BENNING PV 3 to cool down.
The BENNING PV 3 automatically tests connected PV modules, PV strings or PV fields. All measuring
results are displayed on the large LC display.
- Appliance dimensions: (L x W x H) = 340 x 300 x 152 mm
- Appliance weight: 5000 g
- Power supply: 3 x 3.7 V rechargeable lithium-ion batteries
- Interface: USB type B
- Internal memory: up to 999 data records
- Display: LC display with background lighting
- PC software: Download program BENNING Datalogger (CSV format)
- Radio range to BENNING SUN 2: 30 m in open space, frequency: 433 MHz
6. Environment conditions
- The BENNING PV 3 is intended for making measurements in dry environment.
- Maximum barometric elevation for making measurements: 2000 m,
- Over voltage category/ Siting category: IEC/ EN 61010-1 →1500 V for systems without a specified
measuring category,
- Pollution Class 2,
- Protection Class: IP 40 (DIN VDE 0470-1, IEC/ EN 60529) with the cover being open
IP 40 means: Protected against objects >1mm, (4 - first index). No protection against water, (0 - second
index).
IP 64 with the cover being closed
IP 64 means: Protection against access to dangerous parts and protection against solid impurities,
dustproof, (6 - first index). Splash proof, (4 - second index). Can also be used in case of precipitation.
- EMC: IEC/ EN 61326-1,
- Operating temperature and relative humidity: For operating temperature from 0 °C to 40 °C: non-
condensing
- Storage temperature: The BENNING PV 3 can be stored at any temperature in the range from - 25 °C
to + 65 °C (relative humidity from 0 to 90 %). The battery should be taken out of the instrument for
storage.
7. Electrical specifications
Note: The measuring precision is specified as the sum of
- a relative fraction of the measured value and
- a number of digits (counting steps of the least significant digit).
This specified measuring precision is valid for temperatures in the range from 18 °C to 30 °C and relative
humidity less than 80 %.
7.1 PV module/ PV string/ PV field, open-circuit voltage (Vo/c)
Measuring range Resolution Measuring accuracy
5.0 V - 1500 V 0.1 V ± (0.5 % + 2 digits)
7.2 PV module/ PV string/ PV field, short-circuit current (Is/c)
Measuring range Resolution Measuring accuracy
0.50 A - 40.00 A
(maximum power: 45 kW)
0.01 A ± (1 % + 2 digits)
8. Measuring with the BENNING PV 3
8.1 Preparation for measuring
Operate and store the BENNING PV 3 only at the specified storage and operating temperatures conditions.
Do not permanently expose the device to sunlight.
- Strong sources of interference in the vicinity of the BENNING PV 3 can lead to unstable readings and
measuring errors.

Table of Contents

Other manuals for Benning PV 3

Related product manuals