4.5 CHIMNEY SUPPORT INSTALLATION
UNIVERSAL ROOF SUPPORT
This support has three possible uses:
1. For Secure Temp
ASHT+
/ Nova Temp
HT6103+
and Secure Temp
S2100+
/ Nova
Temp
HT6000+
, it must be used on a roof to support the chimney.
2. It may be used on a floor, ceiling or roof above an offset to support the chimney
above the offset.
3. It may be used on a floor, ceiling or roof as a supplementary support when the
chimney height exceeds 15 ft. (4.6 m.).
Table 6 gives maximum height of supported chimney.
NOTE: For the ACBI chimney, a support section (ACBI7SL) must be used every 30
ft. (10 m) or the universal support (AC10SU) every 20 ft.
For roof support installation, refer to the instructions provided with the support.
UNIVERSAL OFFSET SUPPORT
This support is used to support the chimney above an offset. When the chimney offset
is used to traverse a wall this support may be used on the wall to support the chimney.
The maximum heights are given in Table 6. For offset support installation, refer to the
instructions provided with the support.