53
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
7008 2028 / 9 OHL R/WS Stop mode in the event of the drive overheating OHF
Factory setting: 1
0 = "nO": Ignored
1 = "YES": Freewheel stop
6 = "rMP": Stop on ramp
7 = "FSt": Fast stop
7009 2028 / A OLL R/WS Stop mode in the event of a motor overload OLF
Factory setting: 1
0 = "nO": Ignore
1 = "YES": Freewheel stop
6 = "rMP": Stop on ramp
7 = "FSt": Fast stop
7010 2028 / B SLL R/WS Stop mode in the event of a Modbus serial link interuption SLF
WARNING
LOSS OF CONTROL
If the "SLL" parameter is set to 0, communication monitoring will be inhibited. For safety
reasons, "SLL" parameter should be restricted to the debug phase or to special
applications.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Factory setting: 1
0 = "nO": Ignored
1 = "YES": Freewheel stop
6 = "rMP": Stop on ramp
7 = "FSt": Fast stop
This parameter does not apply to the PowerSuite software workshop.
7011 2028 / C COL R/WS Stop mode in the event of a CANopen serial link interuption COF
WARNING
LOSS OF CONTROL
If the "COL" parameter is set to 0, communication monitoring will be inhibited. For safety
reasons, the "COL" parameter should only be used for adjustment or special applications
purpose.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Factory setting: 1
0 = "nO": Ignored
1 = "YES": Freewheel stop
6 = "rMP": Stop on ramp
7 = "FSt": Fast stop
7012 2028 / D tnL R/WS Configuration of auto-tuning status tnF
Factory setting: 1
0 = "nO": Ignored (the drive reverts to the factory settings)
1 = "YES": Drive locks if auto-tuning is unsuccessful.
If rSC (see page 29) is other than nO, tnL is forced to YES.