Blue Box - 9
ELECTRICAL CHARACTERISTICS Refrigerant R407C
MODEL SIGMA 2002 3.2 4.2 5.2 6.2
Maximum absorbed power
(1)
kW 16,4 19,4 24,4 27,3
Maximum starting current A 115 150 145 175
Full load current
(2)
A 34 40 50 54
Power supply V/f/Hz
Control power supply V/f/Hz
400/3~/50
230/~/50
MODEL SIGMA 2002 7.2 8.2 9.2 10.2
Maximum absorbed power
(1)
kW 30,2 36,2 41,4 46,6
Maximum starting current A 179 210 250 265
Full load current
(2)
A 58 70 85 100
Power supply V/f/Hz
Control power supply V/f/Hz
400/3~/50
230/~/50
MODEL SIGMA 2002 12.2 13.2 14.4 16.4
Maximum absorbed power
(1)
kW 51,6 56,6 60,4 72,4
Maximum starting current A 320 339 237 280
Full load current
(2)
A 119 138 116 140
Power supply V/f/Hz
Control power supply V/f/Hz
400/3~/50
230/~/50
MODEL SIGMA 2002 18.4 20.4 24.4 26.4
Maximum absorbed power
(1)
kW 82,8 93,2 103,2 113,2
Maximum starting current A 335 365 439 477
Full load current
(2)
A 170 200 238 276
Power supply V/f/Hz
Control power supply V/f/Hz
400/3~/50
230/~/50
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size
the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the