EasyManua.ls Logo

Blue Box SIGMA 2002 - User Manual

Blue Box SIGMA 2002
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SIGMA 2002
42 ÷ 297 kW
00620062
00620062
0062
Water chillersWater chillers
Water chillersWater chillers
Water chillers
Water/waterWater/water
Water/waterWater/water
Water/water
Scroll compressorsScroll compressors
Scroll compressorsScroll compressors
Scroll compressors
self containedself contained
self containedself contained
self contained
Installation,Installation,
Installation,Installation,
Installation,
operating,operating,
operating,operating,
operating,
and maintenanceand maintenance
and maintenanceand maintenance
and maintenance
manualmanual
manualmanual
manual
ISO 9001 - Cert. n. 0201
ManualManual
ManualManual
Manual
101130A02 101130A02
101130A02 101130A02
101130A02
Issue
12.02 12.02
12.02 12.02
12.02
Replaces
09.98 09.98
09.98 09.98
09.98

Table of Contents

Questions and Answers

  • B
    bennettdebbieSep 13, 2025
    How to turn on my Blue Box SIGMA 2002 if the main power switch is Off?
    • J
      Jeremy SmithSep 13, 2025
      If the main power switch is off (position "O"), turn the mains power selector to position "I".
  • J
    Jeremy StricklandAug 25, 2025
    What to do if my Blue Box SIGMA 2002 compressor is not running and the display is on with alarm “L1” and/or “L2”?
    • R
      Roy HayesAug 25, 2025
      If compressor 1 and/or 2 are not working, and the display shows alarm “L1” and/or “L2”, it could be due to: * A completely empty refrigerant circuit. Check the refrigerant circuit with a leak detector after pressurizing to approximately 4 bar. Repair the leak, apply vacuum, and charge the circuit. * A faulty low-pressure switch. Check and replace if necessary. * A clogged metallic coil filter, resulting in low airflow (only LC/HP). Clean the filter with compressed air. * A clogged refrigerant filter. Check and replace if necessary. * A faulty water circulator pump. Check and replace if necessary.
  • T
    Tina SanchezAug 27, 2025
    What to do if my Blue Box SIGMA 2002 compressor is not running and the display is on with alarm “C1” and/or “C2”?
    • A
      Aaron ThompsonAug 27, 2025
      If compressor 1 and/or 2 are not working and the display shows alarm “C1” and/or “C2”, it could be due to: * Insufficient refrigerant charge. Find the leak with a leak detector, repair it, and recharge the circuit. * A locked 4-way valve. Replace the valve. * Lack of oil. Check the quantity of oil in the circuit and replenish as necessary. Ensure the circuit has all necessary measures to ensure oil return to the compressor. * Condenser entering water temperature is too high. Check the temperature and flow of condenser entering water.
  • K
    Kimberly StewartAug 29, 2025
    What does it mean if there is ice on the liquid refrigerant pipe of my Blue Box SIGMA 2002?
    • T
      Tina MiddletonAug 29, 2025
      Ice forming on the liquid refrigerant pipe can be caused by: * A clogged liquid refrigerant filter. Replace the filter. * A valve on the liquid refrigerant line (if present) not being completely open. Fully open the valve.
  • T
    Travis ZimmermanAug 31, 2025
    What does it mean when my Blue Box SIGMA 2002 compressors run constantly?
    • G
      Gregory LivingstonAug 31, 2025
      If the compressors run constantly, it could be due to: * An incorrectly set or faulty operating thermostat. Check the setting and replace the thermostat if necessary. * A lack of refrigerant gas charge. Check and recharge if necessary. * Excess thermal load. Reduce the thermal load.
  • H
    htuckerSep 1, 2025
    What should I do if my Blue Box SIGMA 2002 is making anomalous noises?
    • E
      Erik Solomon MDSep 1, 2025
      If you notice anomalous noises from the system: * If the compressor is noisy, contact a service organization for a check and replacement if necessary. * If the thermostatic valve is noisy, contact a service organization for a check and to replenish the refrigerant charge. * If pipes are vibrating, contact a service organization to secure the pipelines. * If casing panels vibrate, check that the panels are properly fastened; contact a service organization if necessary.
  • V
    vmcgeeNov 27, 2025
    What causes insufficient capacity in my Blue Box SIGMA 2002 Chiller, even though the display is on without alarms?
    • L
      Luis CampbellNov 27, 2025
      Insufficient capacity, with the display on but no alarms, can stem from: * Insufficient refrigerant charge: Check refrigerant circuits with a leak detector, repair any leaks, and recharge the circuit. * Presence of moisture in the refrigerant circuit: Replace the refrigerant filter and, if necessary, dehydrate and recharge the circuit. * One compressor failing to start, with the power circuit open and compressor contactor energized: Find and eliminate the cause of the protection intervention; change the fuses. If the fuses blow immediately, replace the compressor. * A compressor failing to start, with fuses OK but the compressor contactor de-energized: Check voltage across the compressor contactor coil and continuity of the coil; if necessary, replace the coil. * A 4-way reversi...
  • D
    derek26Sep 15, 2025
    What to check if my Blue Box Chiller compressor isn't running and the display is off due to no power to control circuits?
    • D
      David PonceSep 15, 2025
      If there is no power to the control circuits, check the condition of fuses FU50, FU51, and FU52. Also, check the operation of the transformer.
  • T
    theresa95Sep 12, 2025
    What does it mean if my Blue Box SIGMA 2002 compressor is not running and the display is On, with alarm "E3" or "E5"?
    • H
      hvegaSep 12, 2025
      If the compressor is not running and the display shows alarm "E3" or "E5", it could indicate: * Faulty or disconnected resistance RK3 or RK4 (only version LC and LC/HP). Check the resistance and replace if necessary. * Interrupted connections to the pressure sensor (HP version only or if condensation pressure control with fan speed regulator is fitted with version LC and LC/HP). Restore the correct connections to the pressure sensor (“E3” refers to compressor 1, “E5” refers to compressor 2). * A faulty pressure sensor (only on HP version or if condensation pressure control with fan speed regulator is fitted with version LC and LC/HP). Replace the pressure sensor (“E3” refers to compressor 1, “E5” refers to compressor 2).
  • T
    Timothy BakerSep 8, 2025
    What does it mean if my Blue Box Chiller compressor is not running and the display is On with alarm "A1"?
    • M
      Misty ConleySep 8, 2025
      If the compressor is not running and the display shows alarm "A1", it could be due to: * No consent of defrost thermostat due to insufficient water flow rate. Check the hydraulic circuit and wait until the water temperature exceeds the value necessary for the unit to restart. * No consent of defrost thermostat due to insufficient glycol concentration. The programmed set-point is too low for the percentage of glycol in the circuit. Increase the glycol percentage and reduce the defrost set-point.

Summary

Technical Characteristics

Compressors

Details on the hermetic scroll type compressors used in the SIGMA 2002 series units.

Refrigerant Circuit

Description of the refrigerant circuit components and their functions within the unit.

Electrical Panel

Overview of the electrical panel, including main components and control functions.

Technical Data

Safety Precautions

1.2 Safety Rules

Essential safety rules to be followed for operation and maintenance of the unit.

Mechanical Hazards

Analysis of mechanical risks and the solutions adopted to mitigate them.

Electrical Hazards

Identification of electrical risks and compliance with safety standards.

Installation

Electrical Connections

Start-Up

5.1 Preliminary Checks

Essential checks to perform before starting the unit for the first time.

Unit with mCHILLER Microprocessor (models from 3.2 to 13.2)

Starting the Unit

8.3 Starting the Unit

Procedure for starting the unit using the microprocessor controller.

Stopping the Unit

Emergency Stop

Troubleshooting

Unit with pCO2 Microprocessor (models from 14.4 to 26.4)

Checks During Operation

10.1 Checking the refrigerant charge

Procedure for checking the refrigerant charge using sight glass and pressure gauges.