Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 77
controller functions are activated.
The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminates
normally because the defrost end pressure has been reached. In any event, the alarms historical file will contain
a record of all defrost cycles that were terminated forcibly due to a timeout intervention.
Consecutive defrost cycles must be at least 30 minutes apart. If a forced defrost signal persists inform the Service
organisation.