Preparing for installation
AW 4 | 5 | 7 OR-S – 6721866761 (2023/06)
8
▶ For freestanding heat pumps (not near buildings or on a roof):
- Protect the intake side with a wall or similar.
Fig. 14 Free standing heat pump
▶ Do not position the heat pump in a location where its front is exposed
to the wind.
▶ The heat pump must not be positioned where there is a risk of large
amounts of snow or water sliding down from the house roof. If this
cannot be avoided, a protective roof must be installed.
– Install the roof at least 1000 mm above the heat pump.
3.3 Positioning clearances
Fig. 15 Recommended space between the heat pump and surrounding solid objects (mm)
[*] Minimum clearance. The space can be reduced on the back and
one of the sides at the same time or only at the front, but please
note that this may lead to a higher noise level and/or a lower
thermal performance.
10
0
0
1000
≥
2000
(
≥
800*)
1000
≥
2000
(≥800*)
≥400
(≥
200*)
≥
2000
(
≥
400*)
≥
2000 (800*)
≥400
(≥
200*)
1000
1000
1000
1
000
1
000
1000
1
0
00
1
0
00
0010038327-006
10
0
0
10
0
0
≥400
(≥
200*)